Optional hold-down clips are available to secure blank panels in the grid.
NOTE: Gordon does not recommend grid systems for use with fan powered modules (FFU’s). Consider Gordon rod-suspended grid systems for FFU applications.
LG-10

LG-15

LG-20

Extruded Grid Components
- 6063 T-5 aluminum alloy
Finishes
- Clear satin anodized for harsh environments
- Pearl White powder coat
- Antimicrobial
Factory Applied Gaskets
- Closed-cell polyethylene foam, 2# density
- Fungus-resistant (Method 508.1 Mil Std 810-C)
- Flame-resistant (FMYSS #302; burn rate 4” per minute)
- Color: Off White
- Contact factory for custom gasket availability
Grid Layout Modules
- 2′ x 4′
- 2′ x 2′
- Metric or custom module sizes can be provided
LG Application Guidelines
- Appropriate for cleanrooms designed to: ISO-7 (Class 10,000) or higher
- Use ducted terminal filter modules
- Use cleanroom standard size filters and light fixtures
Suspension And Load Data
- Minimum 12 gauge hanger wire (furnished by others)
- Hanger Wire Spacing:
- 4’ o.c. for panels up to 5 lbs. per square foot
- At all 4 corners of filter module and light fixture location
- Load test recommendations outlined in the brochure should not be exceeded, nor should the components be deflected more than 1/360th of their span.