Data Center Structural Ceiling Grid

Gordon invented structural ceiling grid for the data center industry. Over a decade later, Gordon continues to develop products that the industry requires to manage the new reality presented with higher density requirements.
Features & Benefits
- Attach anywhere on the ceiling grid using the 3/8” screwslot
- Flexibility to attach utilities, cable trays, containment and walls wherever needed
- Proven reliability with some of the highest load capabilities in the industry
- Suspend from structure in 4×4 or 4×6 configurations
Design Attributes
- Finishes: Clear Anodized or Powder Coated
- Standard Module Sizes: 2×4 (nominal), 4×4 (nominal)
- Standard and Heavy Duty Turnbuckles available to meet load requirements
- Fixed or Floating perimeters available
- Meets BS EN13964:2014
- Meets ASTM E580
Gordon Grid Pro™ incorporates advanced profile geometry and strategically engineered stiffeners to deliver enhanced structural strength to support overhead cable and power distribution, wall systems, and containment barriers.
Imperial (North America)
Gordon Grid Pro™ is the next generation of Data Center Ceilings.
Imperial Data Grid Structural Suspension – Gordon Grid Pro™ is designed to provide load support for overhead cable and power distribution, wall systems, and containment barriers.


|
Main Tee Spacing |
Hanger Spacing |
Deflection |
Max Concentrated Static Load at Mid-Span |
Max Linear Load Based on Deflection Shown |
|---|---|---|---|---|
|
48″ |
48″ |
L/360 (.133″) |
357 lbs |
143 lbs/ft |
|
48″ |
48″ |
L/180 (.266″) |
714 lbs |
286 lbs/ft |
Metric (EMEA)


|
Main Tee Spacing |
Hanger Spacing |
Deflection |
Max Concentrated Static Load at Mid-Span |
Max Linear Load Based on Deflection Shown |
|---|---|---|---|---|
|
1200 mm |
1200 mm |
L/360 (3.33 mm) |
168 kg |
224 kg/m |
|
1200 mm |
1200 mm |
L/180 (6.67 mm) |
336 kg |
448 kg/m |
Gordon Grid Max™ has the integrity to span 4 feet, 6 feet, and 8 feet. Meet the highest required loads with the strongest aluminum structural ceiling system in the industry. Whether the structure is steel or precast, Gordon Grid Max™ can carry the load.
Designing For Hyperscale
Gordon Grid Max™ is designed to exceed the requirements of Hyperscale and Cloud data center operators. As rack connectivity and power loads increase, higher load capacities are needed for overhead deployment inside the data hall. At the same time, trending away from access floor use increases demand for more open plenum space above the ceiling. Gordon Grid Max™ achieves these goals.


Imperial (North America)
Gordon Grid Max™ is the next generation of Data Center Ceilings.
Imperial Data Grid Structural Suspension – Gordon Grid Max™ is designed to provide load support for overhead cable and power distribution, wall systems, and containment barriers.


|
Main Tee Spacing |
Hanger Spacing |
Max. Allowable Deflection |
Max. Concentrated Static Load at Mid-Span |
|---|---|---|---|
|
48″ |
48″ x 48″ |
L/180 (.266″) |
1965 lbs * |
|
48″ |
48″ x 72″ |
L/180 (.4″) |
1089 lbs |
|
48″ |
48″ x 48″ |
L/360 (.133″) |
1217 lbs |
*Load @ Max Yield Strength of the Tee
Metric (EMEA)


|
Main Tee Spacing |
Hanger Spacing |
Max. Allowable Deflection |
Max. Concentrated Static Load at Mid-Span |
|---|---|---|---|
|
1200 mm |
600 mm x 600 mm |
L/360 (1.44 mm) |
1443 kg |
|
1200 mm |
1200 mm x 1200 mm |
L/360 (3.33 mm) |
415.73 kg |
|
1200 mm |
1200 mm x 1800 mm |
L/360 (5 mm) |
183 kg |
|
1200 mm |
1200 mm x 2400 mm |
L/360 (6.66 mm) |
104 kg |
*Load @ Max Yield Strength of the Tee