DATA CENTER

CEILING SYSTEMS

DESIGN ATTRIBUTES
  • Load Bearing Design - The DG 1.5 ceiling suspension is engineered to support direct suspension of overhead cable distribution and containment barriers.
  • All extrusions have a continuous 3/8-16 thread boss for connection and suspension at any location
  • Intersection connectors join the extruded aluminum grid members and provide an attachment point for 4' x 4' suspension from building structure
  • Perimeters can be fixed or floating
  • Finish - Clear Anodized
CEILING OPTIONS:
  • PANELS
    • DataVENT open cell, aluminum panels for hot air return
    • Corrugated, perforated metal acoustical panels
    • Twin wall polycarbonate panels
    • Non-perforated metal panels
  • DataLUME LAY-IN LIGHT TROFFERS are available in T-8 flourescent or LED lamp options
  • DataCEL CONTAINMENT WALL SYSTEM - Patent No.: US 8,713,869 B1
  • LOAD ADAPTER - For transitioning to various hangar rod diameters
  • SEAL - Available with optional factory applied gasket to minimize air leakage.
  • SECURITY - Optional hold-down clips secure panels in place
CEILING SUSPENDED LOADING:
  • Ceiling supports over 110 lbs/SF with 2X safety factor = 55 lbs/SF
  • 4' span between trapeze suspension = 480 lbs / 2 suspension points = 240 lbs point load
  • Single point average pull-out from screwslot = 950 lbs with 2X safety factor applied = 475 lbs
Internap Data Center Ceiling
DWG | DXF | PDF
Cyber Innovation Data Center Ceiling Cyber Innovation Data Center Ceiling with Suspended Cable Tray