DataCel II

GORDON - I NC .COM 80 0 . 747. 895 4 FA X 80 0 . 87 7. 8746 3 5023 HAZEL JONES ROAD, BOSSIER CI T Y, L A 71111 SLIDING DOOR Frame Material 6063 T-6 Temper Aluminum Tensile Strength 30,000 psi Paneling - Corrugated hollow Plastic Sheet (Standard) Material Polycarbonate based on Bisphenol A Color Clear Thickness 1/4” Self-ignition temperature: 450° C (842° F) Odor Odorless Meets or exceeds ASTM E84-01 Measuring For Rigid Containment Filling gaps between cabinets: Measure the width and height of the gap. DataCEL II will typically be built 0.5” narrower than the actual width of the gap and include compressible foam bulb for both sides of the panel. Hot aisle chimney º Distance from the top of cabinets to the ceiling º Height of all cabinets, in-row cooling units of UPS systems in the row º Are there units with different heights down the row? If so leveling kits and rigid walls can be used to create more rows. º Aisle width (from cabinet frame to cabinet frame. If aisle width varies use widest point as measurement) º Ceiling type (drop grid, structural threaded grid, slab, etc.) º Check for obstructions such as cable trays, lights, sprinkler pipes, cables, etc. above racks, beams or posts in the aisle. Will these obstructions need to pass through the containment, be moved, or have the containment go around? Typical chimney layout º Panels are typically supported by the cabinets or suspended from structural ceiling grid or rod. º If panels are supported by cabinets an adjustable bracket with foam seal can be run along the top of the panels to seal to the ceiling. IN-FILL PANELS Paneling - LuciteLux (Optional) Material Acrylic sheet Color Clear Self-ignition temperature: 650° F Odor Odorless Meets or exceeds ASTM E84

RkJQdWJsaXNoZXIy NDExNjIx