GASKETED GRIDS

RG CLEANROOM GRID

RG Grid Cleanroom Ceiling

Applications include pharmaceutical, food processing, and hospital industries. The RG system differs from the CG system in that the 1-1/2" extruded aluminum face tee is designed with an 1/4" upturned flange and provides a sharp architectural detail. Panels or filters contact the gasket first to complete a seal prior to settling on the tee flange. RG provides an upgrade in performance over the more economical CG System.

Finishes

  • Clear satin anodized aluminum for harsh environments.
  • White high performance powder coat.
  • Optional ACROSTATTM antimicrobial powder coat.
  • Custom finishes.

Gasketing

The standard RG Series gasket is a factory applied, 1/4" x 1/2" closed cell PVC, gray in color, with small cells and a smooth surface. Gaskets are available with adhesive on one or both sides; polyvinyl, neoprene, polyethylene; anti-bacterial, and flame retardant. Call Gordon if custom gaskets are required.

RG Grid Intersection

Gasket Specifications

  • Passes fungus resistance test (Method 508.1 mill-std-810C)
  • Flame-resistant (FMYSS #302)
  • Shore Hardness (ASTM D-2240) on AA scale is 7; on OO scale is 51
  • 8# density per cubic foot
  • U.S.D.A. approved

Filter Compatibility

RG systems ar compatible with all major filter manufacturers.

Light Fixture Compatibility

RG systems require fixtures designed specifically for cleanroom applications.

Custom Panels

Custom .032" aluminum panels are manufactured in all sizes to allow for non-standard module sizes, fill-in perimeter panels, and sprinkler panels.

RG Profile Detail DWG | DXF | PDF
RG Profile Detail
RG Assembly Detail DWG | DXF | PDF
RG Assembly Detail
Accessories
RGHC Hold Down Clip
RGHC Hold Down Clip
RG Hanger Clip
RG Hanger Clip
90 Degree Angle Clip
90 Degree Angle Clip
RG Accessories
MTS-Main Tee Splice 1 per main tee
RG-2
Two Way Clips
1 per cross tee
RGHC
Hold Down Clips
as needed for panel security / usually 4 per module
90° Angle Clip tee attachment to wall angle
RG Sliding
Hanger Clips
optional hanger clip slides along web of the tee allowing hanger wire attachment when special clearances for filters or fixtures are required
RG Load Table
System
Type
Web
Height
Span Hanger
Wire Spacing
Spacing of
Main Tees
Applied Load
(lbs./sq.ft.)
ASTM
RG-15 1-3/4" 48" 24"
48"
8.9
4.4
Heavy Duty
Heavy Duty
RG Parts Specifications
Part Number
Description
A
Web Depth
B
Exposed
Gasketed
Flange
Length
Weight per
linear ft.
w/ gasket
Pieces per
carton
w/ gasket
Linear feet
per carton
RG-15-MT4 Main Tee 1-3/4" 1 1/2" 12' 0.31 16 192
RG-15-MT2 Main Tee 1-3/4" 1 1/2" 12' 0.31 16 192
RG-15-48CN Cross Tee
Center
Notch
1-3/4" 1 1/2" 4' 0.31 48 192
RG-15-48NN Cross Tee
No Notch
1-3/4" 1 1/2" 4' 0.31 48 192
RG-15-24 Cross Tee 1-3/4" 1 1/2" 2' 0.31 48 96
RG-WA-48 Wall Angle 1-1/2" 3/4" 12' 0.23 24 288
RG-WA-24 Wall Angle 1-1/2" 3/4" 12' 0.23 24 288